Inspection instructions for a Broaster Ventless Fryer Fire Suppression System
Click here for a printable copy - See page 3
Broaster Company VF-2 / VF-3i 12-Year Inspection
Inspection must be performed by certified service personnel, as per NFPA 17A
- Install Safety Pin into suppressant canister valve before servicing Fire
Suppression System - Perform Semi-Annual inspection
- Remove Fire Suppressant Canister
- Discharge and discard fire suppressant from canister
- Perform Hydrostatic test of the empty canister
a. While canister is removed, flush out the fire suppressant tubes and
nozzles - If canister passes the hydrostatic test, refill with suppressant and pressurize to
195 psi and re-install - Properly tag the fire suppressant canister with date tested
- If canister fails the hydrostatic test, replace with Broaster Part Number 15991
a. Canister must be shipped empty, it will have to be filled and pressurized
before installation.
See Related Article:How to perform a semi-annual inspection on a Broaster Ventless Fryers
Ensure that any discrepancies that might affect the safe operation of this unit are resolved before tagging the unit as safe to use.