How to perform a 12-Year inspection on a Broaster Ventless Fryer

Inspection instructions for a Broaster Ventless Fryer Fire Suppression System

 

Click here for a printable copy - See page 3

Broaster Company VF-2 / VF-3i 12-Year Inspection


Inspection must be performed by certified service personnel, as per NFPA 17A

  1. Install Safety Pin into suppressant canister valve before servicing Fire
    Suppression System
  2. Perform Semi-Annual inspection
  3. Remove Fire Suppressant Canister
  4. Discharge and discard fire suppressant from canister
  5. Perform Hydrostatic test of the empty canister
    a. While canister is removed, flush out the fire suppressant tubes and
         nozzles
  6. If canister passes the hydrostatic test, refill with suppressant and pressurize to
    195 psi and re-install
  7.  Properly tag the fire suppressant canister with date tested
  8.  If canister fails the hydrostatic test, replace with Broaster Part Number 15991
    a. Canister must be shipped empty, it will have to be filled and pressurized
         before installation.

    See Related Article: 

    How to perform a semi-annual inspection on a Broaster Ventless Fryers

Ensure that any discrepancies that might affect the safe operation of this unit are resolved before tagging the unit as safe to use.